Cubicle types

The type-tested substation is primarily used in the decentralised energy distribution sector in the automotive sector and in industry.

There are numerous cubicle variants, which can be used to provide the optimal customised solution for the many requirements in a project.

MS – medium-voltage cell (air-insulated)

  • Rated voltage max. 24 kV (13.8 kV)
  • Rated current to 630 A
  • Rated short-time withstand current 31.5 kA / 1s
  • Protection class IP4X

TGE – Transformer housing

  • Rated voltage (medium voltage) max. 24 kV
  • Rated short-time withstand current (medium voltage) 31.5 kA
  • Rated insulation voltage (low voltage) 1,000 V
  • Rated current (low voltage) up to max. 2,500 A
  • Protection class IP2X

NMS – machine network cabinet

  • Rated insulation voltage 1,000 V
  • Rated current 2,300 A
  • Protection class IP4X

NHS – high current busbar cabinet

  • Rated insulation voltage 1,000 V
  • Rated current 2,500 A
  • Protection class IP4X

NKA – cable distribution cabinet

  • Rated insulation voltage 1,000 V
  • Rated current 2,500 A
  • Protection class IP4X

NKO – compensation cabinet

  • 350 kvar
  • 6-part control stage
  • Detuning to 14%
  • Protection class IP4X
  • Stackable